75
= Key1
= Key 2
= Key 3
= Max. value or consumption = Min. value or supply
Scale
The text "
AnLo
" flas-
hes. Press
key 1.
The text
EDIT
ap-
pears and the first
digit of the scale start
value flashes.
Pressing
key 1 again,
every other digit of the
scale start value or
scale end value can
be selected.
Scale start value and scale end value
Scale start and end value can be set within the
setting range of the corresponding measured value.
With
key 3 you can
change the flashing
number.
with
key 2 the decimal
point can be moved:
In the first digit of the scale start value and the scale
end value. the sign „-“ can be entered. The sign
appears after the number „9“.
After selection of the last number of the scale end
value, the text
EDIT
disappears, and you can change
to the next menu with
key 3.
At a selected output range of 4-20mA, a current of
4mA is effected for -100kW and 20mA for 400kW.
L1
L2
L3
W
EDIT
Scale start value at 0/4mA
Scale end value at 20mA
Sign
Scale start value = - 0.100MW = - 100kW
Scale end value = 400kW
L1
L2
L3
W
M
k
CONF
EDIT
Scale start value (0/4mA)
Scale end value (20mA )
L1
L2
L3
W
EDIT
MODBUS
Diagr. Principle diagram analogue output, selection of scale start value and scale end value.
Measured values
EMAX analogue
outputs 1-4
UMG505
Analogue Outputs
0/4 -
20mA
0/4 -
20mA
0/4 -
20mA
+24V=
0V
12
10
9
8
13
11
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
22 Ohm
Analogue output 4
Analogue output
3
Analogue output 2
Analogue output 1
0/4 -
20mA
Scale start value
Scale end value
L1
V
01