72
= Key1
= Key 2
= Key 3
= Max. value or consumption = Min. value or supply
Pulse width
To each „
digital output
“, that was assigned to
energy, a pulse width and valence can be assigned.
In the manufacturers presettings, the pulse width is
set to 50ms.
The pulse width can be set in the raneg of
50ms to 99,99 seconds.
At pulse width of 50ms, pulses with a maximum
frequeny of 10 Hz can be given out.
Pulses, that cannot be sent, are saved in pulse
memory. The pulse memory can save up to 32000
pulses.
Diagr. Principle diagram for digital outputs
UMG505
Digital Outputs
L1
L2
L3
T
M Wh
LON-Bus
Index 53, Bit 3-7
MODBUS
Adr. 30hex, Bit 1-5
Energy meter
T00-T34
Threshold outputs
1-5
Switching clock outputs
1-5
EMAX digital outputs
1-5
EMAX analogue outputs
1-4
No source assigned
+24V=
36
35
34
33
32
31
Digital
Output
5
Digital
Output
4
Digital
Output
3
Digital
Output
2
Digital
Output
1
Pulse
width
Pulse width
CONF