105
= Key1
= Key 2
= Key 3
= Max. value or consumption = Min. value or supply
Description
Indication
Setting range
Presettings
EMAX
Target 1-5
„
SoLL
“
0W .. 9999MW
0 W
Priority
0 .. 9 (0=off)
0
EMAX-Digital outputs 1-5
„
E.oP
x“
Connection power
0W .. 9999MW
0 W
Min. switch-on time
20 .. 999 seconds
60 seconds
Min. switch-off time
20 .. 999 seconds
60 seconds
Max. disconnection time
20 .. 999 seconds
900 seconds
EMAX analogue outputs 1-4
„
E.An
x“
Consumers
Max. Spare power
0W .. 9999MW
0 W
Run up time
0 .. 999 seconds
0 seconds
Generator
Min. running time
0 .. 999 minutes
0 minutes
Run up time
0 .. 99 seconds
0 seconds
Digital inputs 1-4
„
in
xx“
Input, S0
„
So
“
0Wh .. 9999MWh
Digital outputs 1-5
„
out
x“
Pulse output
„
PuLS
“
00.05 .. 99.99 seconds
0.05 seconds
Analogue output
„
AnLo
“
Measured value
Scale start value
0 .. 9999
0
Scale end value
0 .. 9999
0
LCD contrast
"
cont
"
170 .. 230
185
Inner temperature
"88°"
2-digit
actual inner temperature
Date and time
Date and time
Summer time
"oFF"
oFF, on, Eu
oFF
Winter time
"oFF"
oFF, on, Eu
oFF
User password
"
PASS
"
0000 .. 9999
"0000"
Serial number
"
S. nr
"
8-digit
Producer programmed
Software Release
"
rEL
"
4-digit
loaded Firmware version