60
= Key1
= Key 2
= Key 3
= Max. value or consumption = Min. value or supply
EMAX analogue outputs
The UMG505 has 5 digital and 4 analogue Emax-
outputs internally. Each internal Emax analogue
output can be assigned to an „analogue output“. If a
generator should be controlled by an Emax
analogue output, the internal Emax analogue output
cannot only be assigned to an „Analogue Output“,
but also to a „Digital Output“. The „
Digital Output
“
is active, when the calculated current of the Emax
analogue output is bigger than 0mA. Therefore, this
„Digital Output“ can be used as a starting signal for
generator control.
MODBUS
Diagr. Priciple diagram for the analogue outputs. Selection of source.
Measured values
EMAX analogue
outputs 1-4
UMG505
Analogue Outputs
0/4 -
20mA
0/4 -
20mA
0/4 -
20mA
+24V=
0V
12
10
9
8
13
11
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
22 Ohm
analogue output 4
analogue output 3
analogue output 2
analogue output 1
0/4 -
20mA
Scale start. value
Scale end value
L1
V
01
Attention!
The EMAX analogue outputs must be
assigned to an „Analogue Output“ in the
programming.
EMAX-
analogue output
Maximum connection
power
Consumer/
(Generator)
Minimum connection
power
Priority
W
W
CONF
EMAX-
analogue output
Max. spare power
(Min. running time)
Run up time/
(Run up time)
Priority
CONF
W
For the EMAX analogue outputs, the following
parameters can be set:
Description
Setting range
Priority
: 0 .. 9 (0 = off)
EMAX analogue output
: 1 .. 4
Max. connection power
: 0W .. 9999MW
Min. connection power
: 0W .. 9999MW
Consumer
Max. spare power
: 0W .. 9999MW
Run up time
: 10 .. 9999sec.
Generator
Min. running time
: 0 .. 9999minutes
Run up time
: 0 .. 99seconds