Goodrive350-UL Series VFD
Function parameter list
-220-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
positioning completion signal)
1: Always valid
Bit7: Initial positioning selection (for cyclic
positioning by terminals)
0: Invalid (do not rotate)
1: Valid
Bit8: Positioning enable signal selection (for cyclic
positioning by terminals only; positioning function is
always enabled for automatic cyclic positioning)
0: Pulse signal
1: Level signal
Bit9: Position source
0: P21.17 setting
1: PROFIBUS/CANopen setting
Bit10–11: Reserved
Bit12: Positioning curve selection (reserved)
0: Straight line
1: S curve
P21.17
Position digital
reference
Set digital positioning position;
Actual position=P21.17×P21.11/P21.12
0–65535
0
○
P21.18
Positioning
speed setting
selection
0: Set by P21.19
1: Set by AI1
2: Set by AI2
3: Set by AI3
4: Set by high speed pulse HDIA
5: Set by high speed pulse HDIB
0
○
P21.19
Positioning
speed digits
0–100.0% max. frequency
20.0%
○
P21.20
Acceleration time
of positioning
Set the acceleration/deceleration time of positioning
process.
Acceleration time of positioning means the time
needed for the VFD to accelerate from 0Hz to Max.
output frequency (P00.03).
Deceleration time of positioning means the time
needed for the VFD to decelerate from Max. output
frequency (P00.03) to 0hz.
Setting range of P21.20: 0.01–300.00s
Setting range of P21.21: 0.01–300.00s
3.00s
○
P21.21
Deceleration time
of positioning
3.00s
○