Goodrive350-UL Series VFD
Basic operation instructions
-96-
Function
code
Name
Detailed parameter description
Default
value
17: Set value 2 of PROFIBUS\CANopen
communication
18: Set value 1 of Ethernet
communication
19: Set value 2 of Ethernet
communication
20: Input value of high-speed pulse
HDIB
21: Set value 1 of EtherCAT/PROFINET
communication
22: Torque current (relative to 3 times
the rated current of the motor)
23: Exciting current (relative to 3 times
the rated current of the motor)
24: Set frequency (bipolar)
25: Ramps reference frequency
(bipolar)
26: Running speed (bipolar)
27: Set value 2 of EtherCAT/PROFINET
communication
28: C_AO1 from PLC (You need to set
P27.00 to 1.)
29: C_AO2 from PLC (You need to set
P27.00 to 1.)
30: Running speed (relative to 2 times
the rotating speed of the motor)
31–47: Reserved variable
P06.17
Lower limit of AO1 output
-100.0%–P06.19
0.0%
P06.18
Corresponding AO1 output of
lower limit
0.00V–10.00V
0.00V
P06.19
Upper limit of AO1 output
P06.17–100.0%
100.0%
P06.20
Corresponding AO1 output of
upper limit
0.00V–10.00V
10.00V
P06.21
AO1 output filter time
0.000s–10.000s
0.000s
P06.22–
P06.26
Reserved variable
0–65535
0
P06.27
Lower limit of HDO output
-100.0%–P06.29
0.0%
P06.28
Corresponding HDO output of 0.00–50.00kHz
0.0kHz