Goodrive350-UL Series VFD
Basic operation instructions
-95-
Set value
Function
Description
communication
28
C_AO1 from PLC
1000 corresponds to 100.0%
29
C_AO2 from PLC
1000 corresponds to 100.0%
30
Running speed
0–Two times of rated synchronous speed of motor
31–47
Reserved variable
Related parameter list:
Function
code
Name
Detailed parameter description
Default
value
P06.00
HDO output type
0: Open collector high-speed pulse
output
1: Open collector output
0
P06.14
AO1 output selection
0: Running frequency
1: Set frequency
2: Ramps reference frequency
3: Running speed
4: Output current (relative to 2 times the
rated current of the VFD)
5: Output current (relative to 2 times the
rated current of the motor)
6: Output voltage (relative to 1.5 times
the rated voltage of the VFD)
7: Output power (relative to 2 times the
rated power of the motor)
8: Set torque value (relative to 2 times
the rated torque of the motor)
9: Output torque (relative to 2 times the
rated torque of the motor)
10: Analog AI1 input value
11: Analog AI2 input value
12: Analog AI3 input value
13: Input value of high-speed pulse
HDIA
14: Set value 1 of Modbus
communication
15: Set value 2 of Modbus
communication
16: Set value 1 of PROFIBUS\CANopen
communication
0
P06.15
Reserved variable
0
P06.16
HDO high-speed pulse output
0