Goodrive350-UL Series VFD
Basic operation instructions
-119-
0
1
2
3
4
5
6
7
8
9
10
11
Keypad
AI1
PROFIBUS
MODBUS
PID
Multi-step speed
Simple PLC
HDIA
AI3
AI2
Ethernet
AB pulse string
P00.06
(A frequency command
selection)
Frequency set by
keypad
P00.10
P08.05
Amplitude of wobbling
frequency
*
*
Maintain current
frequency
Set frequency
P00.11 acceleration time 1
P00.12 deceleration time 1
Wobbling
frequency
output
Terminal function 26
wobbling frequency
pause
Terminal function 27
Wobbling frequency reset
Valid
Invalid
Valid
Invalid
HDIB
EtherCat/Profinet
PLC programmable
card
12
13
14
Function
code
Name
Detailed parameter description
Default
value
P00.03
Max. output frequency
P00.03–400.00Hz
60.00Hz
P00.06
A frequency command
selection
0: Set via keypad
1: Set via AI1
2: Set via AI2
3: Set via AI3
4: Set via high speed pulse HDIA
5: Set via simple PLC program
6: Set via multi-step speed running
7: Set via PID control
8: Set via Modbus communication
9: Set via PROFIBUS / CANopen /
DeviceNet communication
10: Set via Ethernet communication
11: Set via high speed pulse HDIB
12: Set via pulse string AB
13: Set via EtherCAT/PROFINET
communication
14: Set via PLC card
0
P00.11
Acceleration time 1
0.0–3600.0s
Depend
on model
P00.12
Deceleration time 1
0.0–3600.0s
Depend
on model
P05.01–
P05.06
Digital input function
selection
26: Wobbling frequency pause (stop at
current frequency)
27: Wobbling frequency reset (revert to
center frequency)
/