Goodrive350-UL Series VFD
Basic operation instructions
-98-
Set
value
Function
Description
uncontrolled by the VFD. This mode is applied in cases of
large-inertia load and free stop time; its definition is the
same with P01.08, and it is mainly used in remote
control.
7
Fault reset
External fault reset function, its function is the same with
the STOP/RST key on the keypad. This function can be
used in remote fault reset.
8
Running pause
The VFD decelerates to stop, however, all the running
parameters are in memory state, eg PLC parameter,
wobbling frequency, and PID parameter. After this signal
disappears, the VFD will revert to the state before stop.
9
External fault input
When external fault signal is transmitted to the VFD, the
VFD releases fault alarm and stops.
10
Frequency increase (UP) Used to change the frequency-increase/decrease
command when the frequency is given by external
terminals.
K1
K2
K3
UP terminal
DOWN terminal
UP/DOWM
Zeroing terminal
COM
The terminal used to clear frequency-increase/decrease
setting can clear the frequency value of auxiliary channel
set by UP/DOWN, thus restoring the reference frequency
to the frequency given by main reference frequency
command channel.
11
Frequency decrease
(DOWN)
12
Clear frequency
increase/decrease setting
13
Switching between A setting
and B setting
This function is used to switch between the frequency
setting channels.
A frequency reference channel and B frequency
reference channel can be switched by no. 13 function;
the combination channel set by P00.09 and the A
frequency reference channel can be switched by no. 14
function; the combination channel set by P00.09 and the
B frequency reference channel can be switched by no. 15
function.
14
Switching between
combination setting and A
setting
15
Switching between
combination setting and B
setting
16
Multi-step speed terminal 1 16-step speeds can be set by combining digital states of
these four terminals.
17
Multi-step speed terminal 2