Goodrive350-UL Series VFD
Function parameter list
-139-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P01.17
Stop speed
detection time
0.00–100.00s
0.50s
◎
P01.18
Running
protection of
power-on
terminal
When the running command channel is controlled by
terminals, the system will detect running terminal
state automatically during power up.
0: Terminal running command is invalid during power
up. The VFD will not run during power up even if the
running command terminal is detected to be valid,
and the system is in running protection state. The
VFD will run only after this terminal is cancelled and
enabled again.
1: Terminal running command is valid during power
up. The system will start the VFD automatically after
initialization is done if the running command terminal
is detected to be valid during power up.
Note:
This function must be set with caution,
otherwise, serious consequences may occur.
0
○
P01.19
Action selection
when the running
frequency is
below lower limit
(lower limit
should be larger
than 0)
This function code is used to set the running state of
VFD when the set frequency is below lower limit
frequency.
0: Run in lower limit of the frequency
1: Stop
2: Sleep
When the set frequency is below lower limit
frequency, the VFD coasts to stop; when the set
frequency is above lower limit again and continues to
be so after the time set by P01.20 elapses, the VFD
will be restored to running state automatically.
0
◎
P01.20
Wake-up-from-sl
eep delay
This function code is used to set the sleep delay.
When the running frequency of VFD is below the
lower limit frequency, the VFD enters sleep state;
when the set frequency is above the lower limit again
and continues to be so after the time set by P01.20
elapses, the VFD will run automatically.
0.0s
○