Goodrive350-UL Series VFD
Function parameter list
-180-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
740.0V;
575V
voltage:
1000.0V
P08.39
Running mode of
cooling fan
0: Common running mode
1: The fan keeps running after power up
0
○
P08.40
PWM selection
0x0000–0x2121
Ones: PWM mode
0: 3PH modulation and 2-phase modulation
1: 3PH modulation
Tens: PWM low-speed carrier limit
0: Limit low-speed carrier to 2K
1: Limit low-speed carrier to 4K
2: No limit on low-speed carrier
Hundreds: Deadzone compensation mode
0: Compensation mode 1
1: Compensation mode 2
Thousands: PWM loading mode
0: PWM loading mode 1
1: PWM loading mode 2
2: Reserved
0x0001
◎
P08.41
Overmodulation
selection
0x00–0x11
Ones
0: Overmodulation is invalid
1: Overmodulation is valid
Tens
0: Mild overmodulation
1: Deepened overmodulation
01
◎
P08.42 Reserved variables
/
/
P08.43 Reserved variables
/
/
P08.44
UP/DOWN
terminal control
setting
0x000–0x221
Ones: Frequency control selection
0: UP/DOWN terminal setting is valid
1: UP/DOWN terminal setting is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: All frequency modes are valid
2: Invalid for multi-step speed when multi-step speed
0x000
○