Goodrive350-UL Series VFD
Basic operation instructions
-80-
Function
code
Name
Detailed parameter description
Default
value
4: Switch over by EtherCAT/PROFINET
communication
Tens: Motor switch-over during running
0: Disable switch-over during running
1: Enable switch-over during running
P12.00
Type of motor 2
0: Asynchronous motor
1: Synchronous motor
0
P12.01
Rated power of
asynchronous motor 2
0.1–3000.0kW
Depend
on model
P12.02
Rated frequency of
asynchronous motor 2
0.01Hz–P00.03 (Max. output frequency) 60.00Hz
P12.03
Rated speed of
asynchronous motor 2
1–36000rpm
Depend
on model
P12.04
Rated voltage of
asynchronous motor 2
0–1200V
P12.05
Rated current of
asynchronous motor 2
0.8–6000.0A
P12.06
Stator resistance of
asynchronous motor 2
0.001–65.535Ω
P12.07
Rotor resistance of
asynchronous motor 2
0.001–65.535Ω
P12.08
Leakage inductance of
asynchronous motor 2
0.1–6553.5mH
P12.09
Mutual inductance of
asynchronous motor 2
0.1–6553.5mH
P12.10
No-load current of
asynchronous motor 2
0.1–6553.5A
P12.15
Rated power of synchronous
motor 2
0.1–3000.0kW
P12.16
Rated frequency of
synchronous motor 2
0.01Hz–P00.03 (Max. output frequency) 60.00Hz
P12.17
Number of pole pairs of
synchronous motor 2
1–50
2
P12.18
Rated voltage of
synchronous motor 2
0–1200V
Depend
on model
P12.19
Rated current of
synchronous motor 2
0.8–6000.0A
Depend
on model
P12.20
Stator resistance of
0.001–65.535Ω
Depend