Goodrive350-UL Series VFD
Function parameter list
-132-
by setting P07.00 to 0; if P01.00 is set to a non-zero value, the parameter will be protected by
password. When modifying function parameters through serial communication, the function of user
password also follows above rules.
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P00 group Basic functions
P00.00
Speed control
mode
0:SVC 0
1:SVC 1
2:SVPWM
3:VC
Note:
If 0, 1 or 3 is selected, it is required to carry out
motor parameter autotuning first.
2
◎
P00.01
Running
command
channel
0: Keypad
1: Terminal
2: Communication
0
○
P00.02
Communication
running
command
channel
0: Modbus
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/PROFINET
4: PLC programmable card
5: Wireless communication card
Note:
1, 2, 3, 4 and 5 are extended functions which
are applicable with corresponding cards.
0
○
P00.03
Max. output
frequency
Used to set the maximum output frequency of the
VFD. It is the basis of frequency setting and the
acceleration/deceleration.
Setting range: Max. (P00.04, 10.00) –630.00Hz
60.00Hz
◎
P00.04
Upper limit of
running
frequency
The upper limit of running frequency is upper limit
value of VFD output frequency. This value cannot be
more than the maximum output frequency.
When the set frequency is higher than the upper limit
frequency, the VFD runs at the upper limit frequency.
Setting range: P00.05–P00.03 (Max. output
frequency)
60.00Hz
◎
P00.05
Lower limit of
running
frequency
The lower limit of running frequency is the lower limit
value of VFD output frequency.
When the set frequency is lower than the lower limit
frequency, the VFD runs at the lower limit frequency.
Note:
Max. output frequency ≥ upper limit frequency
≥ lower limit frequency.
0.00Hz
◎