Goodrive350-UL Series VFD
Function parameter list
-177-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
P08.15
Amplitude of
wobbling
frequency
0.0–100.0% (relative to set frequency)
0.0%
○
P08.16
Amplitude of
jump frequency
0.0–50.0% (relative to amplitude of wobbling
frequency)
0.0%
○
P08.17
Rise time of
wobbling
frequency
0.1–3600.0s
5.0s
○
P08.18
Descend time of
wobbling
frequency
0.1–3600.0s
5.0s
○
P08.19
Switching
frequency of
acceleration/dec
eleration time
0.00–P00.03 (Max. output frequency)
0.00Hz: no switch-over
Switch to acceleration/deceleration time 2 if the
running frequency is larger than P08.19
0.00Hz
○
P08.20
Frequency
threshold of the
start of droop
control
0.00–50.00Hz
2.00Hz
○
P08.21
Reference
frequency of
acceleration/dec
eleration time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note:
Valid for straight acceleration/deceleration
only
0
◎
P08.22
Output torque
calculation mode
0: Calculated based on torque current
0
○
P08.23
Number of
decimal points of
frequency
0: Two decimal points
1: One decimal point
0
○
P08.24
Number of
decimal points of
linear speed
0: No decimal point
1: One
2: Two
3: Three
0
○
P08.25 Set count value P08.26–65535
0
○
P08.26
Designated count
value
0–P08.25
0
○