Function parameter list
-195-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
coefficient of
voltage regulator
during
overvoltage stall
of the bus voltage regulator during overvoltage stall.
Setting range: 0–1000
P11.23
Proportional
coefficient of
current regulator
during
overvoltage stall
This parameter is used to set the proportional
coefficient of the active current regulator during
overvoltage stall.
Setting range: 0–1000
60
○
P11.24
Integral
coefficient of
current regulator
during
overvoltage stall
This parameter is used to set the integral coefficient
of the active current regulator during overvoltage
stall.
Setting range: 0–2000
250
○
P11.25
Enable VFD
overload integral
0: Disabled
1: Enabled
When this parameter is set to 0, the overload timing
value is reset to zero after the VFD is stopped. In this
case, the determination of VFD overload takes more
time, and therefore the effective protection over the
VFD is weakened.
When this parameter is set to 1, the overload timing
value is not reset, and the overload timing value is
accumulative. In this case, the determination of VFD
overload takes less time, and therefore the
protection over the VFD can be performed more
quickly.
0
P11.26–
P11.27
Reserved
variables
0–65536
0
○
P12 group Parameters of motor 2
P12.00 Type of motor 2
0: Asynchronous motor
1: Synchronous motor
0
◎
P12.01
Rated power of
asynchronous
motor 2
0.1–3000.0kW
Depend
on model
◎
P12.02
Rated frequency
of asynchronous
motor 2
0.01Hz–P00.03 (Max. output frequency)
60.00Hz
◎