Goodrive300-16 special inverter for HVAC
Commissioning guidelines
23
Function
code
Name
Set
value
Remark
P06.05
Relay RO3 output
36
Connect motor B variable frequency
P06.06
Relay RO4 output
37
Connect motor B power frequency
P06.07
Relay RO5 output
38
Connect motor C variable frequency
P06.08
Relay RO6 output
39
Connect motor C power frequency
P06.09
Relay RO7 output
41
Connect motor D power frequency
P06.10
Relay RO8 output
43
Connect motor E power frequency
P09.02
Max. PID1 reference
1.000
Adjustable according to the actual
situations
P09.03
Upper limit of PID1
reference
1.000
Adjustable according to the actual
situations
P09.04
Lower limit of PID1
reference
0.100
Adjustable according to the actual
situations
P09.05
PID1 reference
source 1
2
Adjustable according to the actual
situations
P09.09
ACC/DEC time of
PID1 reference
0.000
Adjustable according to the actual
situations
P09.10
PID1 feedback
source 1
1
Adjustable according to the actual
situations
P09.16
Output feature
0
Adjustable according to the actual
situations
P09.17
Proportional gain
1.00
Adjustable according to the actual
situations
P09.18
Integral time
0.10
Adjustable according to the actual
situations
P09.19
Differential time
0.00
Adjustable according to the actual
situations
P22.00
HVAC function
1
HVAC function enabled
P22.01
Hibernation type
1
Hibernate according to the running
frequency
P22.02
Hibernation starting
frequency
40.00Hz
Allow hibernation only when the running
frequency is smaller than the value and