Goodrive300-16 special inverter for HVAC
Appendix A
39
Appendix A Function parameters
For the convenience of function codes setting, the function group number corresponds to the
first level menu, the function code corresponds to the second level menu and the function
code parameter corresponds to the third level menu.
Below is the instruction of the function lists:
The first line
“Function code”: codes of function parameter group and parameters;
The second line
“Name”: full name of function parameters;
The third line
“Detailed instruction of parameters”: detailed instruction of the function
parameters;
The fourth line
“Default value”: the original factory values of the function parameter;
The fifth line
“Modify”: the modifying character of function codes (the parameters can be
modified or not and the modifying conditions), below is the instruction:
“
○
”: means the set value of the parameter can be modified on stop and running state;
“
◎
”: means the set value of the parameter can not be modified on the running state;
“
●
”: means the value of the parameter is the real detection value which can not be
modified.
(The inverter has limited the automatic inspection of the modifying character of the
parameters to help users avoid mismodifying)
A.1 Goodrive300-16 basic function parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P00 Group Basic function group
P00.00
Speed
control
mode
0: Sensorless vector control mode 0
1: Sensorless vector control mode 1
2: V/F control
Note
: Only apply to asynchronous motors
2
◎
P00.01
Run
command
channel
0: Keypad running command
1: Terminal running command channel
2: Communication running command channel
0
○
P00.02
Communic
ation
running
commands
0: MODBUS communication channel
1:
Profibus/CANopen/BACnet/Devicenet
communication channel
2: Ethernet communication channel
0
○