Goodrive300-16 special inverter for HVAC
Appendix A
47
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
frequency
P03.03
Speed loop
proportiona
l gain 2
0~200.0
20.0
○
P03.04
Speed loop
integral
time 2
0.000~10.000s
0.200s
○
P03.05
High
switching
frequency
P03.02~P00.03 (Max. output frequency)
10.00Hz
○
P03.06
Speed loop
output filter
0~8 (corresponds to 0~2
8
/10ms)
0
○
P03.07
Compensat
ion
coefficient
of
electromoti
on slip
50%~200%
100%
○
P03.08
Compensat
ion
coefficient
of braking
slip
50%~200%
100%
○
P03.09
Current
loop
percentage
coefficient
P
0~65535
1000
○
P03.10
Current
loop
integral
coefficient I
0~65535
1000
○
P03.11
Torque
0: Torque control is invalid
0
○