![INVT GD300-16 Operation Manual Download Page 42](http://html1.mh-extra.com/html/invt/gd300-16/gd300-16_operation-manual_2085742042.webp)
Goodrive300-16 special inverter for HVAC
Appendix A
41
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P00.10
Keypad set
frequency
0.00 Hz~P00.03 (Max. output frequency)
50.00Hz
○
P00.11 ACC time 1 0.0~3600.0s
Depend
on
model
○
P00.12 DEC time 1 0.0~3600.0s
Depend
on
model
○
P00.13
Running
direction
0: Runs at the default direction
1: Runs at the reverse direction
0
○
P00.14
Carrier
frequency
setting
1.0~15.0kHz
Depend
on
model
○
P00.15
Motor
parameter
autotuning
0: No operation
1: Rotation autotuning
2: Static autotuning 1(autotune totally)
3: Static autotuning 2(autotune part parameters)
0
◎
P00.16
AVR
function
selection
0: Invalid
1: Valid during the whole procedure
1
○
P00.17
Inverter
type
0: G type
1: P type
0
◎
P00.18
Function
restore
parameter
0: No operation
1: Restore the default value
2: Cancel the fault record
0
◎
P01 Group Start-up and stop control
P01.00 Start mode
0: Start-up directly
1: Start-up after DC braking
2: Start-up after speed tracing
0
◎
P01.01
Starting
frequency
of direct
start
0.00~50.00Hz
0.50Hz
◎