Goodrive300-16 special inverter for HVAC
Appendix A
70
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
BIT5: running rotation speed (rpm on)
BIT6: output power (% on)
BIT7: output torque (% on)
BIT8: PID1 reference (% flickering)
BIT9: PID1 feedback value (% on)
BIT10: input terminals state
BIT11: output terminals state
BIT12: torque set value (% on)
BIT13: pulse counter value
BIT14: reserved
BIT15: PLC and the current stage in multi-step
speed
P07.06
Parameters
state 2
0x0000~0xFFFF
BIT0: AI1 (V on)
BIT1: AI2 (V on)
BIT2: AI3 (V on)
BIT3: HDI frequency
BIT4: motor overload percentage (% on)
BIT5: the inverter overload percentage (% on)
BIT6: ramp frequency given value(Hz on)
BIT7: linear speed
BIT8: AC inlet current (A on)
BIT9: upper limit frequency (Hz on)
BIT10~15: reserved
0x0000
○
P07.07
Parameters
for stopping
state
0x0000~0xFFFF
BIT0: set frequency (Hz on, frequency flickering
slowly)
BIT1: bus voltage (V on)
BIT2: input terminals state
BIT3: output terminals state
BIT4: PID1 reference (% flickering)
BIT5: PID1 feedback value (% on)
0x100F
○