Goodrive300-16 special inverter for HVAC
Appendix A
85
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
10: Reserved
P09.06
PID1
reference
source 2
0: P09.07
1: P09.08
2: AI1
3: AI2
4: AI3
5: HDI
6: Multi-step speed
7: MODBUS
8: Profibus-DP/CANopen/BACnet
9: Ethernet
10: Reserved
0
○
P09.07
PID1
keypad
reference 1
P09.04~P09.03
0.100
○
P09.08
PID1
keypad
reference 2
P09.04~P09.03
0.100
○
P09.09
PID1
reference
ACC/DEC
time
0.0~1000.0s
0.0s
○
P09.10
PID1
feedback
source 1
0: AI1
1: AI2
2: AI3
3: HDI
4: MODBUS
5: Profibus-DP/CANopen/BACnet
6: Ethernet
7: Reserved
0
○
P09.11
PID1
feedback
source 2
0: AI1
1: AI2
2: AI3
3: HDI
0
○