Goodrive300-16 special inverter for HVAC
Commissioning guidelines
22
3.4.2 Commissioning steps of basic functions
1. Check the circuits and ensure proper wiring;
2. P00.18=1, restore to factory default;
3. Input the parameters of motor name plate to P2 group and do motor autotuning;
4. P22.00=1, enable HVAC function;
5. P22.10=1, enable circulation variable frequency motor;
6. According to the actual situations, set multiple function codes of P22.11~P22.18 to 1 and
enable multiple circulation variable frequency motors; set the function codes to 2 and enable
power frequency motors;
7. According to the motor number, such as A and B, set P06 group;
8. Proper running and commissioning
3.4.3 List of control parameters
List of relevant function parameters (take 3 circulation variable frequency 2 power
frequency motors for example)
Function
code
Name
Set
value
Remark
P00.00
Speed control mode
2
V/F control
P00.01
Run command
channel
1
Terminal control, adjustable according to
the actual situations
P00.03
Max. output
frequency
50.00Hz
Adjustable according to the actual
situations
P00.04
Upper limit of
running frequency
50.00Hz
Adjustable according to the actual
situations
P00.05
Lower limit of
running frequency
20.00Hz
Adjustable according to the actual
situations
P00.11
ACC time 1
4.0s
Adjustable according to the actual
situations
P00.12
DEC time 1
4.0s
Adjustable according to the actual
situations
P05.01
S1 terminals function
1
Forward running
P05.02
S2 terminals function
7
Fault reset
P06.03
Relay RO1 output
34
Connect motor A variable frequency
P06.04
Relay RO2 output
35
Connect motor A power frequency