Goodrive300-16 special inverter for HVAC
Appendix A
109
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P18.00
HVAC
function
status
0: Invalid
1: Valid
0
●
P18.01
SN of
running
variable
frequency
motors
0~8
1~8 corresponds to motor A~F, 0 stands for no
valid variable frequency motor and 255 stands for
fixed variable frequency motors
0
●
P18.02
Valid status
of multiple
motors
0x00~0xFF
Bit0~Bit7 stands for motor A~H
0: The corresponding motor is invalid, unavailable
1:
The corresponding motor is valid, available
0x00
●
P18.03
Running
status of
power
frequency
motors
0x00~0xFF
Bit0~Bit7 stands for motor A~H
0: The corresponding motor stops
1:
The corresponding motor is running
0x00
●
P18.04
SN of power
frequency
motors to be
circulated
0~8
1~8 corresponds to motor A~F and 0 stands for no
valid power frequency motor. Only display power
frequency motors to be circulated when in normal
running
0
●
P18.05
Remaining
time of
power
frequency
motors to be
circulated
0.00~600.00h
0.00h
●
P18.06
SN of
variable
frequency
motors to be
circulated
0~8
1~8 corresponds to motor A~F and 0 stands for no
valid variable frequency motor. Only display
variable frequency motors to be circulated when in
normal running
0
●
P18.07 Remaining 0.00~600.00h
0.00h
●