Goodrive300-16 special inverter for HVAC
Appendix C
130
Appendix C Peripherial options and parts
Parts
Model
Remark
Chinese/English LCD keypad
PRD_LCD300-16_ZY
Relay extension board
EC-RL-106
6 NO outputs
PEthernet
communication card
EC-TX-103
CANopen communication card
EC-TX-105
Devicenet communication card
EC-TX-106
BACnet card
EC-TX-107
C.1 Breaker and electromagnetic contactor (optional)
It is necessary to add fuse for the avoidance of overload.
It is appropriate to use a breaker (MCCB) which complies with the inverter power in the
3-phase AC power and input power and terminals (R,S,T). The capacity of the inverter
should be 1.5-2 times of the rated current.
Due to the inherent operating principle and construction of circuit breakers,
independent of the manufacturer, hot ionized gases may escape from the
breaker enclosure in case of a short-circuit. To ensure safe use, special
attention must be paid to the installation and placement of the breakers.
Follow the manufacturer’s instructions.
It is necessary to install the electromagnetic contactor in the input side to control the
switching on and off safety of the main circuit. It can switch off the input power supply when
system fault.
Model
Fuse (A)
Breaker (A)
Rated working current
of the contactor(A)
GD300-16-004G/5R5P-4
30
25
16
GD300-16-5R5G/7R5P-4
45
25
16
GD300-16-7R5G/011P-4
60
40
25
GD300-16-011G/015P-4
78
63
32
GD300-16-015G/018P-4
105
63
50
GD300-16-018G/022P-4
114
100
63
GD300-16-022G/030P-4
138
100
80
GD300-16-030G/037P-4
186
125
95