Goodrive300-16 special inverter for HVAC
Commissioning guidelines
37
Code
Fault
Cause
Solution
fault
the synchronous motors not
set properly.
The autotuning parameter is
not right.
The inverter is not connected
to the motor.
normal.
Check whether the control
parameter is set properly or not.
Increase the maladjustment
detection time.
LL
Electronic
underload
fault
The inverter will report the
underload pre-alarm
according to the set value.
Check the load and the
underload pre-alarm point.
PId1E
Feedback
over limit fault
PID1 feedback value is
larger than upper limit
detection value or smaller
than lower limit detection
value in a long time.
Check PID1 feedback source;
Check PID1 feedback source
signal connection
TI-E
Clock chip
fault
The slot terminal board is
loose.
EEPROM is broken
Check the slot terminal board;
Press STOP/RST to reset;
Change the main control board
E-DP
Profibus-DP
communication
fault
Communication address is
not correct.
Corresponding resistor is not
dialed
The files of main stop GSD
does not set sound
The ambient interference is
too strong.
Check related setting
Check the communication
method selection.
Check the environment and
avoid the interference.
E-NET
Ethernet
communication
fault
The Ethernet address is not
set right.
The Ethernet communication
is not selected to right.
The ambient interference is
too strong.
Check the relative setting.
Check the communication
method selection.
Check the environment and
avoid the interference.
E-CAN
CANopen
The connection is not sound
Check the connection