Goodrive300-16 special inverter for HVAC
Commissioning guidelines
26
Function
code
Name
Set
value
Remark
P22.27
Action of variable
frequency motor
when reducing motor
0
Adjustable according to the actual
situations
P22.28
ACC time of variable
frequency motor
when reducing motor
10.0s
Adjustable according to the actual
situations
P22.29
Multi-motor pressure
loss compensation
0
Adjustable according to the actual
situations
P22.30
Pressure reference
boost value of 1
auxiliary motor
5.0%
Adjustable according to the actual
situations
P22.31
Pressure reference
boost value of 2
auxiliary motors
10.0%
Adjustable according to the actual
situations
P22.32
Pressure reference
boost value of 3
auxiliary motors
15.0%
Adjustable according to the actual
situations
P22.33
Circulation cycle of
power frequency
motor
0.0h
Adjustable according to the actual
situations
P22.34
Circulation cycle of
variable frequency
motor
0.0h
Adjustable according to the actual
situations
P22.35
Circulation
frequency threshold
45.00Hz
Adjustable according to the actual
situations
3.4.4 Instruction of commissioning process
1. If the system of multiple circulation variable frequency motors does not need the auxiliary
power frequency motor, set P22.14 and P22.15 to 0. For the system of multiple circulation
variable frequency multiple auxiliary power frequency motors, set the parameters as
above table and part of the parameters such as PID1 reference according to the actual
situations. For the system of multi-motor in operation at the same time, PID1 feedback