Goodrive300-16 special inverter for HVAC
Appendix A
62
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P05.54
HDI
frequency
input filter
time
0.000s~10.000s
0.010s
○
P06 Group Output terminals
P06.00 HDO output
0: Open collector pole high speed pulse output
1: Open collector pole output
0
◎
P06.01
Y output 0: Invalid
1: In operation
2: Forward rotation operation
3: Reverse rotation operation
4: Jogging operation
5: The inverter fault
6: Frequency degree test FDT1
7: Frequency degree test FDT2
8: Frequency arrival
9: Zero speed running
10: Upper limit frequency arrival
11: Lower limit frequency arrival
12: Ready for operation
13: Pre-magnetizing
14: Overload pre-alarm
15: Underload pre-alarm
16: Completion of simple PLC stage
17: Completion of simple PLC cycle
18: Setting count value arrival
19: Defined count value arrival
20: External fault valid
21: Reserved
22: Running time arrival
23: MODBUS communication virtual terminals
output
0
○
P06.02 HDO output
0
○
P06.03
Relay RO1
output
1
○
P06.04
Relay RO2
output
5
○
P06.05
Relay RO3
output
0
○
P06.06
Relay RO4
output
0
○
P06.07
Relay RO5
output
0
○
P06.08
Relay RO6
output
0
○
P06.09
Relay RO7
output
0
○
P06.10
Relay RO8
output
0
○