Goodrive300-16 special inverter for HVAC
Appendix A
69
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
3: Download the keypad function parameter to local
address (excluding the motor parameter of P02
and P12 group)
4: Download the keypad function parameters to
local address (only for the motor parameter of P02
and P12 group)
P07.02
QUICK/JO
G function
selection
0: No function
1: Jogging
2: Shift the display state by the shifting key
3: Shift between forward rotations and reverse
rotations
4: Clear UP/DOWN settings
5: Coast to stop
6: Shift the given manner of running commands
7: Quick commission mode (committee according
to the non-factory parameter)
1
◎
P07.03
Shifting
sequence
selection of
QUICK/JO
G
commands
0: Keypad control
→terminals control
→communication control
1: Keypad control
←→terminals control
2: Keypad control
←→communication control
3: Terminals control
←→communication control
0
○
P07.04
STOP/RST
stop
function
0: Only valid for the keypad control
1: Both valid for keypad and terminals control
2: Both valid for keypad and communication control
3: Valid for all control modes
0
○
P07.05
Parameters
state 1
0x0000~0xFFFF
BIT0: running frequency (Hz on)
BIT1: set frequency(Hz flickering)
BIT2: bus voltage (Hz on)
BIT3: output voltage(V on)
BIT4: output current(A on)
0x0c1F
○