Goodrive300-16 special inverter for HVAC
Appendix A
43
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
between
FWD/REV
rotation
1:Switch after the starting frequency
P01.15
Stopping
speed
0.00~100.00Hz
0.50Hz
◎
P01.16
Detection
of stopping
speed
0: Detect according to speed setting (no stopping
delay)
1: Detect according to speed feedback (only valid
for vector control)
0
◎
P01.17
Detection
time of
feedback
speed
0.00~100.00s (only valid when P01.16=1)
0.50s
◎
P01.18
Terminal
running
protection
when
powering
on
0: The terminal running command is invalid when
powering on
1: The terminal running command is valid when
powering on
0
○
P01.19
Action if
running
frequency<
lower limit
frequency
(valid >0)
0: Run at the lower-limit frequency
1: Stop
0
◎
P01.21
Restart
after power
off
0: Disable
1: Enable
0
○
P01.22
The waiting
time of
restart after
0.0~3600.0s (valid when P01.21=1)
1.0s
○