SHENZHEN INVT ELECTRIC CO., LTD. CHV160 Operation Manual
36
6. Detail Function Description
Basic Function Group
Function
Code
Name
Description
setting
range
Default
Value
P0.00
Speed
Control
Mode
0
V/F Control
0
0
Selection of Speed Control Mode
0
V/F Control Mode
V/F control mode is suitable for the application which does not require high control
accuracy, and also suitable for cases with one inverter driving multiple motors.
Function
Code
Name
Description
setting
range
Default
Value
P0.01
Operation
command
Path
0
Keyboard Command Path (LED extinct)
1
Terminal Command Path (LED blinking)
2
Communication Command Path (LED light up)
0
2
0
Path Selection for the inverter Control Command
The inverter control commands include: start, stop, forward, reverse, jogging, failure reset
and so on.
0
Keyboard Command Path (LOCAL/REMOT light extinct);
The buttons RUN and STOP/RST on the keyboard are for operation control. Multifunction
key QUICK/JOG, if set up as FWD/REV switching function (P7.03 is set up as 1), can change
the rotating direction; When at operation, pushing RUN and STOP/RST in same time will
make the inverter stop freely.
1
Terminal Command Path (LOCAL/REMOT blinking)
Multifunction input terminals of forward, reverse, forward jogging, reverse jogging and so
on, perform the operation command control.
2
Communication Command Path (LOCAL/REMOT light up)
Operation command control is performed through communication pattern by upper
position machine. If it is chosen, it is a must to use the serial communication interface card
(Optional part) from our company
Function
Code
Name
Description
setting
range
Default
Value
P0.02
Keyboard
and
terminal
UP/DOWN
setting
0
Valid, and the inverter memorizes when
power down
1
Valid, and the inverter does not
memorize when power down
2
Invalid
0
2
0
CHV series inverter can set up the frequency though
and
buttons on the keyboard
and terminal UP/DOWN (Frequency setting increase /Frequency setting decrease), and as it
has the highest purview, it can combine with any other frequency setting path to mainly
accomplishes the fine adjustment of inverter output frequency during control system
commissioning.