SHENZHEN INVT ELECTRIC CO., LTD. CHV160 Operation Manual
58
multifunction I/O extension card.
Multifunction I/O extension card adds one more multifunction relay output terminal and
one more multifunction analog output terminal.
Function
Code
Name
Description
setting
range
Default
Value
P6.00
HDO output
selection
0: open-collector high speed pulse output
1: open-collector output
0
1
0
HDO terminal is programmable diplex terminal.
0: open-collector high speed pulse output: the maximum pulse frequency is 50.0 KHz.
See P6.09 for its associative function.
1: open-collector output: see P6.03 for its associative function
Function
Code
Name
Description
setting
range
Default
Value
P6.01
Y1 output selection
Open collector
output function
0
25
1
P6.02
Y2 output selection
Open collector
output function
0
25
0
P6.03
HDO open collector
output selection
Open collector
output function
0
25
0
P6.04
Relay 1 output
selection
Open collector
output function
0
25
3
P6.05
Relay 2 output
selection
Open collector
output function
0
25
0
P6.06
Relay 3 output
selection
Open collector
output function
0
25
0
Open collector output functions are indicated as following table:
Setting
Value
Function
Description
0
Zero Output
Output terminal has no function
1
Inverter is
running
forward.
Indicates the inverter is running forward with output frequency.
Here output ON signal
2
Inverter is
running reverse
Indicates the inverter is running reverse with output frequency.
Here output ON signal
3
Fault output
Once inverter fault happens, output ON signal
4
Motor overload
pre- warning
Before motor electronic thermal protection is active, it is judged
according to predicted overload value. Once the pre-warning
time is exceeded, output ON signal. Overload parameter is set
up at PB.04-PB.06.
5
Inverter
overload pre-
warning
Based on inverter pre-warning point, once the pre-warning
time is exceeded, output ON signal. Overload parameter is set
up at PB.04-PB.06.
6
Frequency
level detecting
FDT reached
Please refer to the detail description of function code P8.25,
P8.26
7
Frequency
reached
Please refer to the detail description of function code P8.27
8
Null speed
When the inverter output frequency is less than the starting