![INVT CHV160 Operation Manuals Download Page 102](http://html1.mh-extra.com/html/invt/chv160/chv160_operation-manuals_2085685102.webp)
SHENZHEN INVT ELECTRIC CO., LTD. CHV160 Operation Manual
102
Function
Code
Name
Detail Parameter Description
Setting
Range
Defaul
t
Modifi
cation
LCD Display Serial
No.
P9.05
Integral time (Ti)
0.01
10.00s
0.01
10.00
0.10s
Integral time 190.
P9.06
Differential time
(Td)
0.00
10.00s
0.00
10.00
0.00s
Differentia
time
191.
P9.07
Sampling cycle
time (T)
0.01
100.00s
0.01
100.00
0.50s
Sampling
cycle
192.
P9.08
PID control bias
limit
0.0
100.0%
0.0
100.0
0.0%
PID bias.
limit
193.
P9.09
PID output
buffering time
0.00
10.00s
0.00
10.00
0.00
PID buffer
time
194.
P9.10
Feedback broke
detecting value
0.0
100.0%
0.0
100.0
0.0%
FB broke
value
195.
P9.11
Feedback broke
detecting time
0.0
3600.0s
0.0
3600.0
1.0s
FB broke
time
196.
PA Group Multi-Speed
PA.00
Simple PLC
operation mode
0: Stop after running once
1: keep running at the final value
after running once
2: running in cycle
0
2
0
Simple PLC
mode
197.
PA.01
Simple PLC
memory option
0: no memory while power down
1: memorize while power down
0
1
0
PLC
memory opt
198.
PA.02
Multi-Speed 0
-100.0
100.0%
-100.0
100.0
0.0%
Multi-speed
0
199.
PA.03
0
th
Stage operating
time
0.0
6553.5s(h)
0.0
6553.5
0.0s
0
th
stage
time
200.
PA.04
Multi-Speed 1
-100.0
100.0%
-100.0
100.0
0.0%
Multi-speed
1
201.
PA.05
1
st
Stage operating
time
0.0
6553.5s(h)
0.0
6553.5
0.0s
1
st
stage
time
202.
PA.06
Multi-Speed 2
-100.0
100.0%
-100.0
100.0
0.0%
Multi-speed
2
203.
PA.07
2
nd
Stage operating
time
0.0
6553.5s(h)
0.0
6553.5
0.0s
2
nd
stage
time
204.
PA.08
Multi-Speed 3
-100.0
100.0%
-100.0
100.0
0.0%
Multi-speed
3
205.
PA.09
3
rd
Stage operating
time
0.0
6553.5s(h)
0.0
6553.5
0.0s
3
rd
stage
time
206.
PA.10
Multi-Speed 4
-100.0
100.0%
-100.0
100.0
0.0%
Multi-speed
4
207.
PA.11
4
th
Stage operating
time
0.0
6553.5s(h)
0.0
6553.5
0.0s
4
th
stage
time
208.