SHENZHEN INVT ELECTRIC CO., LTD. CHV160 Operation Manual
93
Function
Code
Name
Detail Parameter Description
Setting
Range
Defaul
t
Modifi
cation
LCD Display Serial
No.
P5.02
S1 Terminal
Function Selection
0
39
1
S1 function
62.
P5.03
S2 Terminal
Function Selection
0
39
4
S2 function
63.
P5.04
S3 Terminal
Function Selection
0
39
7
S3 function
64.
P5.05
S4 Terminal
Function Selection
0
39
0
S4 function
65.
P5.06
S5 Terminal
Function Selection
0
39
0
S5 function
66.
P5.07
HDI1 terminal
on-off input
function selection
0
39
0
HDI1
function
67.
P5.08
HDI2 terminal
on-off input
function selection
0
39
0
HDI2
function
68.
P5.09
S6 Terminal
Function Selection
0
39
0
S6 function
69.
P5.10
S7 Terminal
Function Selection
0
39
0
S7 function
70.
P5.11
S8 Terminal
Function Selection
0
No function
1: Forward
2: Reverse
3: 3-wire control
4: Forward Jog
5: Reverse Jog
6: Coast to stop
7: Failure reset
8: Running pause
9: External fault
10: Freq up
11: Freq down
12: Freq up clr
13: Switch setting A and B
14: Switch setting A and A+B
15: Switch setting B and A+B
16: Multi-Speed 1
17: Multi-Speed 2
18: Multi-Speed 3
19: Multi-Speed 4
20: Multi-speed pause
21: ACC/DEC Time1
22: ACC/DEC Time 2
23: PLC reset
24: PLC pause
25: PID pause
26: Traverse pause
27: Traverse reset
28: Counter reset
29: Length reset
30: ACC/DEC disabled
31: Torque control disabled
32-47: Reserved
0
39
0
S8 function
71.
P5.12
DI signal filtering
times
1
10
1
10
5
DI filter
times
72.
P5.13
Terminal control
mode
0: 2-wire mode1
1: 2-wire mode2
2: 3-wire mode1
3: 3-wire mode2
0
3
0
DI control
mode
73.
P5.14
UP/DOWN
Terminal UP/DOWN
frequency increment
variable rate
0.01
50.00Hz/s
0.01
50.00
0.50H
z/s
Freq var rate 74.
P5.15
AI1 lower limit
0.00V
10.00V
0.00
10.00
0.00V
AI1 lower
limit
75.
P5.16
AI1 lower limit
corresponding
setting
-100.0%
100.0%
-100.0
100.0
0.0%
AI1 L limit
set
76.