SHENZHEN INVT ELECTRIC CO., LTD. CHV160 Operation Manual
60
6
Output torque
0-double rated motor current
7
Analog AI1 input
0
10V
8
Analog AI2 input
0
10V/0
20mA
9
Analog AI3 input
0
10V
10
Analog AI4 input
0
10V
11
High speed pulse HDI1 input
0.1
50.0kHz
12
High speed pulse HDI2 input
0.1
50.0kHz
13
Length
0-set length (P8.19)
14
count value
0-set count value (P8.22)
15
20
Reserved
Reserved
Function
Code
Name
Description
setting
range
Default
Value
P6.10
Lower output limit 1
0.0%
100.0%
0.0
100.0
0.0%
P6.11
Lower limit corresponding
AO1 output
0.00V
10.00V
0.00
10.00
0.00V
P6.12
Upper output limit 1
0.0%
100.0%
0.0
100.0
100.0%
P6.13
Upper limit corresponding
AO1 output
0.00V
10.00V
0.00
10.00
10.00V
Above function codes define the relationship between output value and analog output
corresponding output value. When the output value exceeds the maximum output or the
minimum output range, the beyond portion should be calculated with maximum output or
minimum output.
When analog output is current output, 1mA is equivalent to 0.5V
For different applications, the analog output corresponding to 100% output value is different.
For details, please refer to the instruction of each application.
Following figures explain several setting circumstances:
Figure 6-13 The coincidence relationship between assigned value and analog output
Function
Code
Name
Description
setting range
Default
Value
P6.14
Lower output limit 2
0.0%
100.0%
0.0
100.0
0.0%
P6.15
Lower limit corresponding AO2 output 0.00V
10.00V
0.00
10.00
0.00V
P6.16
Upper output limit 2
0.0%
100.0%
0.0
100.0
100.0%
P6.17
Upper limit corresponding AO2 output 0.00V
10.00V
0.00
10.00
10.00V
P6.18
Lower output limit 3
0.0%
100.0%
0.0
100.0
0.0%
P6.19
Lower limit corresponding HDO output 0.0
50.0kHz
0.0
50.0
0.0kHz
P6.20
Upper output limit 3
0.0%
100.0%
0.0
100.0
100.0%
P6.21
Upper limit corresponding HDO output 0.0
50.0kHz
0.0
50.0
50.0kHz