SHENZHEN INVT ELECTRIC CO., LTD. CHV160 Operation Manual
92
Function
Code
Name
Detail Parameter Description
Setting
Range
Defaul
t
Modifi
cation
LCD Display Serial
No.
P2.10
Motor no-load
current
0.01
655.35A
0.01
655.35
Set by
model
No-load
current
46.
P3 Group Reserved
P4 Group V/F Control
P4.00
V/F curve setting
0: Linear
1
Multipoint
2
1.3 order decreasing torque
3
1.7 order decreasing torque
4
2.0 order decreasing torque
0
4
0
V/F curve
set
47.
P4.01
Torque boost
0.0%
auto
0.1
30.0
0.0
30.0
1.0
Torque
boost
48.
P4.02
Torque boost
cut-off point
0.0%
50.0% (Rated freq)
0.0
50.0
20.0%
Torq bst
cut-off
49.
P4.03
V/F Frequency
Point 1
0.00Hz
P4.05
0.00
P4.05
5.00H
z
V/F freq 1
50.
P4.04 V/F Voltage Point 1
0.0%
100.0%
0.0
100.0
10.0%
V/F voltage
1
51.
P4.05
V/F Frequency
Point 2
P4.03
P4.07
P4.03
P4.07
30.00
Hz
V/F freq 2
52.
P4.06 V/F Voltage Point 2
0.0%
100.0%
0.0
100.0
60.0%
V/F voltage
2
53.
P4.07
V/F Frequency
Point 3
P4.05
P2.01
P4.05
P2.01
50.00
Hz
V/F freq 3
54.
P4.08 V/F Voltage Point 3
0.0%
100.0%
0.0
100.0
100.0
%
V/F voltage
3
55.
P4.09
V/F slip
compensation
range
0.00
10.00Hz
0.00
10.00
0.0Hz
V/F slip
comp
56.
P4.10
AVR function
option
0: Invalid
1: Valid
2: Invalid in deceleration
0
2
1
AVR option
57.
P4.11
Energy-saving
operation option
0: Disabled
1: Enabled
0
1
0
Energy-save
oper
58.
P4.12
Reserved function
0~1
0~1
0
Reserved
59.
P5 Group Input
P5.00
HDI input type
option
0: Both pulse
1: HDI1 is DI HDI2 is pulse
2: HDI2 is DI HDI1 is pulse
3: Both DI
0
3
0
HDI type
60.
P5.01
Terminal function
input option
0: DI
1: Communication
0
1
0
Terminal
option
61.