SHENZHEN INVT ELECTRIC CO., LTD. CHV160 Operation Manual
51
P5 Group Input Terminal Group
CHV series inverter standard unit has 6 multi-function digital input terminals (in which
HDI1 can be used as the high speed pulse input terminal) and 2 analogue input terminals. If
the system needs more input and output terminals, a multifunction I/O extension card should
be installed
Function
Code
Name
Description
setting
range
Default
Value
P5.00
HDI input
type
selection
0: HDI1 and HDI2 both are high speed pulse input
1: HDI1 is on-off input and HDI2 is high speed
pulse input
2: HDI2 is on-off input and HDI1 is high speed
pulse input
3: HDI1 and HDI2 are both on-off input
0
3
0
HDI input type selection function code determines HDI1 and HDI2 are high speed pulse
input or on-off input.
Function
Code
Name
Description
setting
range
Default
Value
P5.01
Terminal function
input selection
0: physical on-off input
1: communication virtual terminal input
0
1
0
This function code determines the terminal input channel.
0: physical on-off input, i.e. the on-off signal is input through external terminals.
1: communication virtual terminal input, i.e. the on-off signal is set up through upper
position machine via communication pattern.
Function
Code
Name
Description
setting
range
Default
Value
P5.02
S1 Terminal Function
Selection
Programmable
multifunction terminal
0
39
1
P5.03
S2 Terminal Function
Selection
Programmable
multifunction terminal
0
39
4
P5.04
S3 Terminal Function
Selection
Programmable
multifunction terminal
0
39
7
P5.05
S4 Terminal Function
Selection
Programmable
multifunction terminal
0
39
0
P5.06
S5 Terminal Function
Selection
Programmable
multifunction terminal
0
39
0
P5.07
HDI1 terminal on-off input
function selection
Programmable
multifunction terminal
0
39
0
P5.08
HDI2 terminal on-off input
function selection
Programmable
multifunction terminal
0
39
0
P5.09
S6 Terminal Function
Selection
Programmable
multifunction terminal
0
39
0
P5.10
S7 Terminal Function
Selection
Programmable
multifunction terminal
0
39
0
P5.11
S8 Terminal Function
Selection
Programmable
multifunction terminal
0
39
0
These parameters are used to set up the corresponding functions of digital multifunction