SHENZHEN INVT ELECTRIC CO., LTD. CHV160 Operation Manual
39
Function
Code
Name
Description
setting
range
Default
Value
P0.06
Combined
mode of
setting
source
0
A
1
B
2
A+B
3
Max
A
B
0
3
0
The frequency setting channel is selected through this parameter. The frequency setting
is achieved by combining Frequency Command A and Frequency Command B.
(0, 1, 2) combining modes can be switched by terminal function (P5 Group).
Selecting “A+B” can realize the function of frequency overlap setting. CHV series inverter
can realize mutually switching between frequency setting modes.
Max A B : means that if Frequency Command A is bigger than Frequency Command B,
Frequency Command A is set as the set frequency, and vice versa, Frequency Command B is
set as the set frequency.
Function
Code
Name
Description
setting
range
Default
Value
P0.07
Maximum Output Frequency
10.00
600.00Hz
10.00
600.00
50.00Hz
It is used to set up the maximum output frequency of inverter. Please note that, it is the
basis of frequency setting and acceleration/deceleration speed.
Function
Code
Name
Description
setting
range
Default
Value
P0.08
Upper limit frequency
P0.09
P0.07
maximum
frequency
P0.09
P0.07
50.00Hz
It is the upper limit of inverter output frequency, which should be less than or equal to the
maximum output frequency.
Function
Code
Name
Description
setting
range
Default
Value
P0.09
Lower limit frequency
0.00 Hz
P0.08
(Upper limit frequency)
0.00
P0.08
0.00Hz
The lower limit of inverter output frequency.
It can be chosen through function code P1.14, and acts when the set frequency is lower
than the lower frequency limit: operate at the lower limit frequency, stop or be dormant.
Therein, Maximum output frequency upper limit frequency lower limit frequency.
Function
Code
Name
Description
setting range
Default
Value
P0.10
Keyboard frequency
setting
0.00 Hz
P0.08
(upper limit frequency)
0.00
P0.08
50.00Hz
When Frequency Command A is chosen as “keyboard Setting”, this function code value is
the initial set value of inverter frequency.