Setting
Value
Function
Description
operation
frequency, output ON signal
9
Count pulse
setting value
reached
When the counting value is up to the setting of P8.22, output
ON signal.
10
Assigned count
pulse number
reached
When the counting value reaches the setting value by P8.23,
output ON signal. For Counting function, refer to FB Group
function description.
11
Length reached
When the actual length detected exceeds the set value by
P8.19, output ON signal.
12
PLC circulation
completed
When the simple PLC operation finishes one circulation, output
a pulse signal with a width 200ms.
13
Operating time
reached
The cumulated operation time of inverter exceeds the time set
by P8.24, output ON signal.
14
Upper limit
frequency
reached
When the operating frequency reaches the upper frequency
limit, output ON signal.
15
Lower limit
frequency
reached
When the operating frequency reaches the lower frequency
limit, output ON signal.
16
ready for
operation
When the inverter is at ready status for operation with main
circuit and control circuit power supplied and the inverter
protection function not actuated, output ON signal.
17
Start boost
motor 1
18
Start boost
motor 2
In the case of simple water supply system with one inverter
driving three pumps, it is for the control of the two boost
pumps. For its detail description, please refer to the
descriptions of function code P8.29, P8.30 and P8.31
19~25
Reserved
Reserved
Function
Code
Name
Description
setting
range
Default
Value
P6.07
AO1 output selection
Multifunction analog output
0
20
0
P6.08
AO2 output selection
Multifunction analog output
0
20
0
P6.09
HDO open collector high speed pulse
output selection
Multifunction high speed
pulse output
0
20
0
The standard analog output is 0-20mA (or 0-10V). Current or voltage output can be selected
by Jumper J9. HDO open collector high speed pulse output range is set as 0 KHZ to 50.0 KHz.
Its corresponding value range is shown as following table:
Setting
Value
Function
Range
0
Operating frequency
0-maximum output frequency
1
Setting frequency
0-maximum output frequency
2
Motor speed
0-double rated motor speed
3
Output current
0-double rated inverter current
4
Output voltage
0-double rated inverter voltage
5
Output power
0-double rated power