Acceleration/Deceleration time can be chosen to be P0.11, P0.12 or above three time
settings. Their meanings are all the same; please refer to P0.11 and P0.12 related description.
The Acceleration/Deceleration time 0-3 at inverter operation can be chosen through
different combination of multifunction digital input terminals.
Function
Code
Name
Description
setting
range
Default
Value
P8.06
Jogging operation frequency
0.00~P0.07
0.00
P0.07 5.00Hz
P8.07
Jogging operation Acceleration time
0.0
3600.0s
0.0
3600.0
20.0s
P8.08
Jogging operation Deceleration time
0.0
3600.0s
0.0
3600.0
20.0s
It is to define the inverter set frequency and Acceleration/Deceleration time at Jogging
operation. START/STOP operation in the inching operation process is performed by direct
start mode and Deceleration stop mode.
The Jogging Acceleration time is the time required for inverter to accelerate from 0Hz to
the maximum output frequency (P0.07).
The Jogging Deceleration time is the time required for inverter to decelerate from the
maximum output frequency (P0.07) to 0Hz.
Function
Code
Name
Description
setting
range
Default
Value
P8.09
Skip frequency 1
0.00
P0.07
0.00
P0.07
0.00Hz
P8.10
Skip frequency 2
0.00
P0.07
0.00
P0.07
0.00Hz
P8.11
Skip frequency range
0.00
P0.07
0.00
P0.07
0.00Hz
When the set frequency is within the skip frequency range, the actual operating frequency
will be operated near the boundary of skip frequency range.
By means of setting skip frequency, the inverter can keep away from the mechanical
resonance point of the load. This inverter has two skip frequency points available. If these two
skip frequencies are both set to 0, this function will be inactive.
Figure 6-15 Skip frequency schematic diagram
Function
Code
Name
Description
setting
range
Default
Value
P8.12
Traverse frequency range
0.0
100.0%
relative to set
frequency
0.0
100.0
0.0%