4.4 Specification Table of Breaker, Cable and Contactor
Model No.
Circuit Braker
(A)
Input/Output
coppery wire)
Contactor rated
current(A)(380V or 220V)
CHV160-004G-2
40
6
25
CHV160-5R5G-2
63
6
32
CHV160-7R5G-2
100
10
63
CHV160-011G-2
125
25
95
CHV160-015G-2
160
25
120
CHV160-018G-2
160
25
120
CHV160-022G-2
200
35
170
CHV160-030G-2
200
35
170
CHV160-037G-2
200
35
170
CHV160-045G-2
250
70
230
CHV160-5R5G-4
25
4
16
CHV160-7R5G-4
40
6
25
CHV160-011G-4
63
6
32
CHV160-015G-4
63
6
50
CHV160-018G-4
100
10
63
CHV160-022G-4
100
16
80
CHV160-030G-4
125
25
95
CHV160-037G-4
160
25
120
CHV160-045G-4
200
35
135
CHV160-055G-4
200
35
170
CHV160-075G-4
250
70
230
CHV160-090G-4
315
70
280
CHV160-110G-4
400
95
315
CHV160-132G-4
400
150
380
CHV160-160G-4
630
185
450
CHV160-185G-4
630
185
500
CHV160-200G-4
630
240
580
CHV160-220G-4
800
150x2
630
CHV160-250G-4
800
150x2
700
CHV160-280G-4
1000
185x2
780
CHV160-315G-4
1200
240x2
900
4.5 Wiring of Main Circuit
4.5.1 Power Supply Connection of Main Circuit
4.5.1.1 Breaker
Between 3ph AC power supply and power input terminals (R, S, T), it is necessary to
connect a breaker which is compatible with the capacity of inverter. The capacity of breaker is
1.5-2 times to the rated current (amperage) of inverter. For details, please refer to
Specification Table of Breaker, Cable, and Contactor
4.5.1.2 Magnetic Contactor
In case of system malfunction and that the power input of inverter must be cut off
completely for safety, magnetic contactor can be installed at the power input side to control the
on/off of the main circuit power supply.
4.5.1.3 Input AC Reactor
In case of high voltage input from power grid and so heavy current flowing into power
supply circuit damages components of rectifier
it is necessary to install and connect a AC