Intel® Server System S9200WK Product Family Setup and Service Guide
50
4.
Insert the DIMM into the slot (see Letter C) pushing down on the DIMM, until the ejection tabs snap
into place (see Letter D). Ensure that the ejection tabs are firmly in place (see Letter E).
4.10.2
Liquid Cooled Compute Module DIMM Replacement
The DIMM replacement procedure for a liquid cooled compute module requires removal, replacement, and
re-installation of several components. The documented procedure should be followed in the order specified
with little or no deviation.
1.
Remove the select compute module from the server chassis (see Section 4.2.1)
2.
Remove the air duct from the computer module (see Section 4.8.1).
4.10.2.1
DIMM Removal
The liquid cooled compute modules within the Intel® Server System S9200WK product family include a
memory replacement tool located on top of the cold plates of the liquid cooling loop. This tool can be used
to remove the DIMM retainer clips in memory configurations that require them, and to open the DIMM
ejection tabs.
Figure 52. Locating and retrieving the memory replacement tool
1.
Locate the memory replacement tool on top of the CPU0 cold plate.
2.
Remove the tool from one of its sides first (see Letter A) and then lift it away (see Letter B).