Intel® Server System S9200WK Product Family Setup and Service Guide
45
4.7.2
Liquid Cooling Loop Installation
1.
Carefully unpack the new liquid cooling loop.
2.
Carefully place the liquid cooling loop assembly into the compute module, ensuring that both the
DIMM cooling assembly and processor cold plates are properly aligned with the mounting screw
holes.
Figure 44. Securing the cross head screws
3.
Place and secure the ten phillips head screws indicated in Figure 44 with a phillips head screwdriver
using 8 lbs. of torque.
Figure 45. Securing the T-20 screws
4.
Using a cross pattern for each cooling plate, place and secure the eight Torx* head screws as
indicated in Figure 45 with a Torx* T-20 screwdriver using 8 lbs. of torque
1
2
3
4
3
2
4
1