Intel® Server System S9200WK Product Family Setup and Service Guide
58
4.14
Chassis Plumbing Assembly Replacement (Liquid Cooled Systems Only)
Select system configurations within the Intel® Server System S9200WK product family support liquid cooling
on the installed compute modules through an integrated liquid cooling loop.
The coolant flow for the liquid cooling loop is supported through liquid cooling plumbing connections
installed in the back of the server chassis. Should the chassis plumbing or plumbing connections become
damaged or worn out, the following sections provide the instructions necessary to remove and replace the
chassis plumbing assembly.
Required Tools and Supplies:
•
Anti-static wrist strap and conductive foam pad (recommended)
•
Phillips head screwdriver
4.14.1
Chassis Plumbing Assembly Removal
1.
Power the system down, remove it from the rack and place it on a flat surface.
Important Safety Note:
Due to the weight of a fully configured system, Intel® recommends using a
mechanical lift to aid with the removal of the system from the rack, and/or to use at least two people to
remove the system from the rack, or remove all installed compute modules from the system before
attempting to remove the system from the rack.
2.
Remove the power supplies (see Section 4.12.1).
3.
Remove the system fans (see Section 4.13.1).
4.
Remove the EMP module / EMP module blank (see Section 3.4).
Figure 65. Removing the quick connect fillers
1.
Remove the fillers located above the quick connect couplings in the back of the chassis.