Description of Function Codes
MD380 User Manual
- 148 -
Function Code
Parameter Name
Setting Range
Default
F0-16
Carrier frequency adjusted with
temperature
0: No
1: Yes
1
It is used to set whether the carrier frequency is adjusted based on the temperature. The
AC drive automatically reduces the carrier frequency when detecting that the heatsink
temperature is high. The AC drive resumes the carrier frequency to the set value when the
heatsink temperature becomes normal. This function reduces the overheat alarms.
Function Code
Parameter Name
Setting Range
Default
F0-17
Acceleration time 1
±V)
±V)
±V)
Model
dependent
F0-18
Deceleration time 1
±V)
±V)
±V)
Model
dependent
Acceleration time indicates the time required by the AC drive to accelerate from 0 Hz to
"Acceleration/Deceleration base frequency" (F0-25), that is, t1 in Figure 6-2.
Deceleration time indicates the time required by the AC drive to decelerate from
"Acceleration/Deceleration base frequency" (F0-25) to 0 Hz, that is, t2 in Figure 6-2.
Figure 6-2 Acceleration/Deceleration time
Time (t)
2XWSXWIUHTXHQF\
(Hz)
Frequency reference
Acceleration/Deceleration
base frequency
t1
t2
Set deceleration time
Actual acceleration time
Actual deceleration time
Set acceleration time
The MD380 provides totally four groups of acceleration/deceleration time for selection. You
can perform switchover by using a DI terminal.
Group 1: F0-17, F0-18
Group 2: F8-03, F8-04
Group 3: F8-05, F8-06
Group 4: F8-07, F8-08
efesotomasyon.com
Summary of Contents for MD380 Series
Page 8: ...efesotomasyon com...
Page 9: ...1 Safety Information and Precautions efesotomasyon com...
Page 16: ...Safety Information and Precautions MD380 User Manual 16 efesotomasyon com...
Page 17: ...2 Product Information efesotomasyon com...
Page 28: ...Product Information MD380 User Manual 28 efesotomasyon com...
Page 29: ...3 Mechanical and Electrical Installation efesotomasyon com...
Page 46: ...Mechanical and Electrical Installation MD380 User Manual 46 efesotomasyon com...
Page 47: ...4 Operation Display and Application Examples efesotomasyon com...
Page 82: ...Operation Display and Application Examples MD380 User Manual 82 efesotomasyon com...
Page 83: ...5 Function Code Table efesotomasyon com...
Page 138: ...Function Code Table MD380 User Manual 138 efesotomasyon com...
Page 139: ...6 Description of Function Codes efesotomasyon com...
Page 249: ...7 EMC efesotomasyon com...
Page 261: ...8 Selection and Dimensions efesotomasyon com...
Page 293: ...9 Maintenance and Troubleshooting efesotomasyon com...