Description of Function Codes
MD380 User Manual
- 146 -
Function Code
Parameter Name
Setting Range
Default
F0-08
Preset frequency
0.00 to maximum frequency
50 Hz
,IWKHIUHTXHQF\VRXUFHLVGLJLWDOVHWWLQJRUWHUPLQDO83'2:1WKHYDOXHRIWKLVSDUDPHWHU
is the initial frequency of the AC drive (digital setting).
Function Code
Parameter Name
Setting Range
Default
F0-09
Rotation direction
0: Same direction
1: Reverse direction
0
You can change the rotation direction of the motor just by modifying this parameter without
changing the motor wiring. Modifying this parameter is equivalent to exchanging any two of
89:FDEOHVRIWKHPRWRU
Note
The motor will resume running in the original direction after parameter initialization. Do not use
this function in applications where changing the rotating direction of the motor is prohibited after
system commissioning is completed.
Function Code
Parameter Name
Setting Range
Default
F0-10
Maximum frequency
50.00–500.00 Hz
50.00 Hz
:KHQWKHIUHTXHQF\VRXUFHLV$,SXOVHUHIHUHQFH',RUPXOWLUHIHUHQFHRIWKH
input corresponds to the value of this parameter.
Function Code
Parameter Name
Setting Range
Default
F0-11
Source of frequency
upper limit
0: Set by F0-12
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: Communication reference
0
It is used to set the source of the frequency upper limit, including digital setting (F0-12), AI,
pulse reference or communication reference. If the frequency upper limit is set by means
of AI1, AI2, AI3, DI5 or communication, the setting is similar to that of the main frequency
source X. For details, see the description of F0-03.
For example, to avoid runaway in torque control mode in winding application, you can set
WKHIUHTXHQF\XSSHUOLPLWE\PHDQVRIDQDORJLQSXW:KHQWKH$&GULYHUHDFKHVWKHXSSHU
limit, it will keep running at this speed.
Function Code
Parameter Name
Setting Range
Default
F0-12
Frequency upper limit
Frequency lower limit (F0-14) to
maximum frequency (F0-10)
50.00 Hz
This parameter is used to set the frequency upper limit.
efesotomasyon.com
Summary of Contents for MD380 Series
Page 8: ...efesotomasyon com...
Page 9: ...1 Safety Information and Precautions efesotomasyon com...
Page 16: ...Safety Information and Precautions MD380 User Manual 16 efesotomasyon com...
Page 17: ...2 Product Information efesotomasyon com...
Page 28: ...Product Information MD380 User Manual 28 efesotomasyon com...
Page 29: ...3 Mechanical and Electrical Installation efesotomasyon com...
Page 46: ...Mechanical and Electrical Installation MD380 User Manual 46 efesotomasyon com...
Page 47: ...4 Operation Display and Application Examples efesotomasyon com...
Page 82: ...Operation Display and Application Examples MD380 User Manual 82 efesotomasyon com...
Page 83: ...5 Function Code Table efesotomasyon com...
Page 138: ...Function Code Table MD380 User Manual 138 efesotomasyon com...
Page 139: ...6 Description of Function Codes efesotomasyon com...
Page 249: ...7 EMC efesotomasyon com...
Page 261: ...8 Selection and Dimensions efesotomasyon com...
Page 293: ...9 Maintenance and Troubleshooting efesotomasyon com...