Description of Function Codes
MD380 User Manual
- 208 -
Function Code
Parameter Name
Setting Range
Default
F9-63
Protection upon load lost
0: Disabled
1: Enabled
0
F9-64
Load lost detection level
0.0%–100.0% (rated
motor current)
10.0%
F9-65
Load lost detection time
0.0–60.0s
1.0s
If protection upon load lost is enabled, when the output current of the AC drive is lower
than the detection level (F9-64) and the lasting time exceeds the detection time (F9-65),
the output frequency of the AC drive automatically declines to 7% of the rated frequency.
During the protection, the AC drive automatically accelerates to the set frequency if the load
resumes to normal.
Function Code
Parameter Name
Setting Range
Default
F9-67
2YHUVSHHGGHWHFWLRQYDOXH
0.0%–50.0% (maximum frequency)
20.0%
F9-68
2YHUVSHHGGHWHFWLRQWLPH
0.0–60.0s
1.0s
This function is valid only when the AC drive runs in the CLVC mode.
If the actual motor rotational speed detected by the AC drive exceeds the maximum
frequency and the excessive value is greater than the value of F9-67 and the lasting time
exceeds the value of F9-68, the AC drive reports Err43 and acts according to the selected
fault protection action.
If the over-speed detection time is 0.0s, the over-speed detection function is disabled.
Function Code
Parameter Name
Setting Range
Default
F9-69
Detection level of too large speed
feedback error
0.0%–50.0% (maximum
frequency)
20.0%
F9-70
Detection time of too large speed
feedback error
0.0–60.0s
5.0s
This function is valid only when the AC drive runs in the CLVC mode.
If the AC drive detects the deviation between the actual motor rotational speed detected by
the AC drive and the set frequency is greater than the value of F9-69 and the lasting time
exceeds the value of F9-70, the AC drive reports Err42 and according to the selected fault
protection action.
If F9-70 (Detection time of too large speed deviation) is 0.0s, this function is disabled.
efesotomasyon.com
Summary of Contents for MD380 Series
Page 8: ...efesotomasyon com...
Page 9: ...1 Safety Information and Precautions efesotomasyon com...
Page 16: ...Safety Information and Precautions MD380 User Manual 16 efesotomasyon com...
Page 17: ...2 Product Information efesotomasyon com...
Page 28: ...Product Information MD380 User Manual 28 efesotomasyon com...
Page 29: ...3 Mechanical and Electrical Installation efesotomasyon com...
Page 46: ...Mechanical and Electrical Installation MD380 User Manual 46 efesotomasyon com...
Page 47: ...4 Operation Display and Application Examples efesotomasyon com...
Page 82: ...Operation Display and Application Examples MD380 User Manual 82 efesotomasyon com...
Page 83: ...5 Function Code Table efesotomasyon com...
Page 138: ...Function Code Table MD380 User Manual 138 efesotomasyon com...
Page 139: ...6 Description of Function Codes efesotomasyon com...
Page 249: ...7 EMC efesotomasyon com...
Page 261: ...8 Selection and Dimensions efesotomasyon com...
Page 293: ...9 Maintenance and Troubleshooting efesotomasyon com...