MD380 User Manual Operation, Display and Application Example
- 65 -
The relationship between the frequency reference and the main frequency source and
auxiliary frequency source is set in F0-07, as follows:
1. Main frequency source X: The main frequency source is directly used to set the frequency
reference.
2. Auxiliary frequency source Y: The auxiliary frequency source is directly used to set the
frequency reference.
3. X and Y superposition: X+Y, X-Y, maximum of X and Y, and minimum of X and Y.
4. Frequency switchover: A DI terminal is used to switch over amongst the preceding three
frequency reference setting modes.
The following figure shows how to set the relationship in F0-07, in which the bold line
indicates the default setting.
Figure 4-19 Relationship between the frequency reference and main and auxiliary frequency
sources
Auxiliary
frequency
source Y
F0-05
F0-06
F0-07
(unit's digit)
Final frequency
reference
Main
frequency
source X
+
--
Max
Min
0
1
2
3
0
1
2
3
4
F0-07
(ten's digit)
F4-00 to F4-09
18
DI1 to DI10
Frequency
switchover
X
Y
XY
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
2 1 0
F0-02 (Command
source selection)
9 frequency
setting
channels
Frequency
source selection
Frequency source
superposition
Frequency source
switchover
Binding command source
to frequency source
Final frequency
reference
Amplitude
limit
F0-27 (default value: 000)
Hundred's digit
(Communication)
Ten's digit
(Terminal)
8QLW
's digit
(
2SHUDWLRQSDQHO
)
Superposition between the main frequency source and the auxiliary frequency source can
be used for closed-loop speed control. For example, using the main frequency source
for setting the main frequency reference and the auxiliary frequency source for automatic
adjustment, in conjunction with switchover performed by the external DI terminal signal, the
required closed-loop control can be implemented.
4.8.3 Binding Command Source to Frequency Source
The three command sources can be separately bound to frequency sources in F0-27, as
VKRZQLQ)LJXUH:KHQWKHVSHFL¿HGFRPPDQGVRXUFH)LVERXQGWRDIUHTXHQF\
source (corresponding digit in the value of F0-27), the frequency reference is determined by
the frequency setting channel set in F0-27. In this case, both main and auxiliary frequency
sources are ineffective.
efesotomasyon.com
Summary of Contents for MD380 Series
Page 8: ...efesotomasyon com...
Page 9: ...1 Safety Information and Precautions efesotomasyon com...
Page 16: ...Safety Information and Precautions MD380 User Manual 16 efesotomasyon com...
Page 17: ...2 Product Information efesotomasyon com...
Page 28: ...Product Information MD380 User Manual 28 efesotomasyon com...
Page 29: ...3 Mechanical and Electrical Installation efesotomasyon com...
Page 46: ...Mechanical and Electrical Installation MD380 User Manual 46 efesotomasyon com...
Page 47: ...4 Operation Display and Application Examples efesotomasyon com...
Page 82: ...Operation Display and Application Examples MD380 User Manual 82 efesotomasyon com...
Page 83: ...5 Function Code Table efesotomasyon com...
Page 138: ...Function Code Table MD380 User Manual 138 efesotomasyon com...
Page 139: ...6 Description of Function Codes efesotomasyon com...
Page 249: ...7 EMC efesotomasyon com...
Page 261: ...8 Selection and Dimensions efesotomasyon com...
Page 293: ...9 Maintenance and Troubleshooting efesotomasyon com...