Description of Function Codes
MD380 User Manual
- 200 -
Function Code
Parameter Name
Setting Range
Default
F9-02
Motor overload pending
FRHI¿FLHQW
50%–100%
80%
7KLVIXQFWLRQLVXVHGWRJLYHDSHQGLQJVLJQDOWRWKHFRQWUROV\VWHPYLD'2EHIRUHPRWRU
overload protection. This parameter is used to determine the percentage, at which pending
is performed before motor overload. The larger the value is, the less advanced the pending
will be.
:KHQ WKH DFFXPXODWLYH RXWSXW FXUUHQW RI WKH$& GULYH LV JUHDWHU WKDQ WKH YDOXH RI WKH
RYHUORDG LQYHUVH WLPHODJ FXUYH PXOWLSOLHG E\ ) WKH '2 WHUPLQDO RQ WKH$& GULYH
DOORFDWHGZLWKIXQFWLRQ0RWRURYHUORDGSHQGLQJEHFRPHV21
Function Code
Parameter Name
Setting Range
Default
F9-03
2YHUYROWDJHVWDOOJDLQ
0 (no stall overvoltage)–100
0
F9-04
2YHUYROWDJHVWDOOSURWHFWLYHYROWDJH
120%–150%
130%
:KHQWKH'&EXVYROWDJHH[FHHGVWKHYDOXHRI)2YHUYROWDJHVWDOOSURWHFWLYHYROWDJH
during deceleration of the AC drive, the AC drive stops deceleration and keeps the present
running frequency. After the bus voltage declines, the AC drive continues to decelerate.
)2YHUYROWDJHVWDOOJDLQLVXVHGWRDGMXVWWKHRYHUYROWDJHVXSSUHVVLRQFDSDFLW\RIWKH
AC drive. The larger the value is, the greater the overvoltage suppression capacity will be.
In the prerequisite of no overvoltage occurrence, set F9-03 to a small value.
)RUVPDOOLQHUWLDORDGWKHYDOXHVKRXOGEHVPDOO2WKHUZLVHWKHV\VWHPG\QDPLFUHVSRQVH
ZLOOEHVORZ)RUODUJHLQHUWLDORDGWKHYDOXHVKRXOGEHODUJH2WKHUZLVHWKHVXSSUHVVLRQ
result will be poor and an overvoltage fault may occur.
If the overvoltage stall gain is set to 0, the overvoltage stall function is disabled. The
overvoltage stall protective voltage setting 100% corresponds to the base values in the
following table:
7DEOH2YHUYROWDJHVWDOOSURWHFWLYHYROWDJHVHWWLQJFRUUHVSRQGVWREDVHYDOXHV
Voltage Class
Corresponding Base Value
Single-phase 220 V
290 V
Three-phase 220 V
290 V
Three-phase 380 V
530 V
Three-phase 480 V
620 V
Three-phase 690 V
880 V
Function Code
Parameter Name
Setting Range
Default
F9-05
2YHUFXUUHQWVWDOOJDLQ
0–100
20
F9-06
2YHUFXUUHQWVWDOOSURWHFWLYHFXUUHQW
100%–200%
150%
:KHQWKHRXWSXWFXUUHQWH[FHHGVWKHRYHUFXUUHQWVWDOOSURWHFWLYHFXUUHQWGXULQJDFFHOHUDWLRQ
deceleration of the AC drive, the AC drive stops acceleration/deceleration and keeps the
present running frequency. After the output current declines, the AC drive continues to
accelerate/decelerate.
efesotomasyon.com
Summary of Contents for MD380 Series
Page 8: ...efesotomasyon com...
Page 9: ...1 Safety Information and Precautions efesotomasyon com...
Page 16: ...Safety Information and Precautions MD380 User Manual 16 efesotomasyon com...
Page 17: ...2 Product Information efesotomasyon com...
Page 28: ...Product Information MD380 User Manual 28 efesotomasyon com...
Page 29: ...3 Mechanical and Electrical Installation efesotomasyon com...
Page 46: ...Mechanical and Electrical Installation MD380 User Manual 46 efesotomasyon com...
Page 47: ...4 Operation Display and Application Examples efesotomasyon com...
Page 82: ...Operation Display and Application Examples MD380 User Manual 82 efesotomasyon com...
Page 83: ...5 Function Code Table efesotomasyon com...
Page 138: ...Function Code Table MD380 User Manual 138 efesotomasyon com...
Page 139: ...6 Description of Function Codes efesotomasyon com...
Page 249: ...7 EMC efesotomasyon com...
Page 261: ...8 Selection and Dimensions efesotomasyon com...
Page 293: ...9 Maintenance and Troubleshooting efesotomasyon com...