Terminating a Defrost Cycle
The defrost cycle terminates automatically when the coil temperature is
greater than or equal to 58°F (14°C) or the defrost timer expires. Defrost can
also be terminated by turning the unit off and back on.
N
No
otte
e:: If Rail Alternate is set YES, the defrost cycle terminates at 70°F (21°C)
or if the defrost timer expires.
Selecting Cycle Sentry or Continuous Mode
When Cycle Sentry Mode is selected, the unit will start and stop
automatically to maintain setpoint, keep the engine warm, and the battery
charged. When Continuous Mode is selected, the unit starts automatically
and runs continuously to maintain setpoint and provide constant airflow.
IIm
mp
po
orrtta
an
ntt:: Cycle Sentry or Continuous Mode may not be selectable if
OptiSet Plus is in use.
See S
Se
elle
eccttiin
ng
g C
Cy
ycclle
e S
Se
en
nttrry
y o
orr C
Co
on
nttiin
nu
uo
ou
uss M
Mo
od
de
e () for an overview of the
procedure.
If the unit is operating in Cycle Sentry Mode, the Cycle Sentry Icon will be
present in the upper right corner of the display as shown below. If the Cycle
Sentry Icon (
) is not present the unit is operating in
Continuous Mode.
Figure 56.
Cycle Sentry Icon
If allowed by OptiSet Plus, Cycle Sentry Mode or Continuous Mode is
selected by pressing the Cycle Sentry/Continuous Key as shown (
).