99
ifm
Device Manual SmartSPS AC14 with EtherNet/IP interface (AC1421, AC1422), Firmware 3.1.2
2015-11-30
Menu
Interfaces
>
Set the device-specific parameters
15909
The parameters can only be changed if the configuration mode is set to
Independent
(
→
Set
the configuration mode
(
To set the device-specific parameters: set the number of channels to be transmitted per analogue
input slave:
1 Select the menu page
►
>
>
►
Select [Parameter] tab.
2 Set the number of analogue channels per input slave
►
Set the following parameter as required:
Parameter
Meaning
Possible values
[Analog. channels/I-slave] Number of analogue
channels transmitted per
input slave
1 channel per A/B
= 1 channel per A/B slave
OR:
channels 1 + 3 per single slave
1 channel
=
1 channel per single slave
OR:
1 channel per A slave
2 channels
=
2 channels per single slave
OR:
2 channels per A slave
4 channels
=
4 channels per single slave
OR:
2 channels per A/B slave
3 Set the number of analogue channels per output slave
►
Set the following parameter as required:
Parameter
Meaning
Possible values
[Analog.
channels/O-slave]
Number of analogue
channels transmitted per
output slave
1 channel per A/B
= 1 channel per A/B slave
OR:
channels 1 + 3 per single slave
1 channel
=
1 channel per single slave
OR:
1 channel per A slave
2 channels
=
2 channels per single slave
OR:
2 channels per A slave
4 channels
=
4 channels per single slave
OR:
2 channels per A/B slave